56 ECOM0010 - User manual
Modbus
address
Description
Read
Write
Reset
value
1007
Led status (0=o, 1=on)
Bit0 = Red led
Bit1 = Yellow led
Bit2 = Green led
RO 0
1008
Alarm status (0=absent, 1=present)
Bit0 = Alarm 1
RO 0
1009
Error ags
Bit0 = Cold junction error
Bit1 = Process error (sensor)
Bit2 = Error in eeprom writing
Bit3 = Error in eeprom reading
Bit4 = Error missing calibration
Bit5 = Generic error
Bit6 = Hardware error
Bit7 = Error H.B.A.* (SSR in short circuit)
Bit8 = Error H.B.A.* (SSR/open charge)
Bit9 = Error H.B.A.* (partial break of the
charge)
RO 0
1010
Cold junction temperature (degree with
tenth)
RO ?
1011 Hot output percentage (0-10000) R/W 0
1012 Cold output percentage (0-10000)
RO
0
1013
Current transformer value (ampere with
tenth)
RO ?
1014
Current transformer ON (ampere with
tenth)
RO ?
1015
Current transformer OFF (ampere with
tenth)
RO ?
1016 Push button status RO 0
1017 Dip value RO 0
2001 Parameter 1 R/W EEPROM